The electromechanical characteristics of an induction machine play a key role in analyzing its performance. These characteristics are usually represented by the torque–speed curve or the relationship between torque and current. They are highly valuable to designers and engineers because they reveal the real behavior of the motor under different operating conditions. The induction motor test is one of the main methods to obtain this data and includes procedures such as locked-rotor tests and no-load tests.

These experiments allow accurate evaluation of the motor’s equivalent circuit parameters. Through them, essential features such as starting torque and speed variation under different loads can be determined. Comparing analytical models with the experimental data obtained from induction motor testing shows that laboratory results are more reliable and precise, providing a solid foundation for the analysis of induction machines.

With the development of motor speed control systems and advanced data acquisition tools, it is now possible to apply precise speed profiles and record the machine’s instantaneous responses. This approach not only reproduces the real conditions of motor startup and loading but also allows detailed examination of its electromechanical behavior across the entire operating range. Consequently, the limitations of analytical or equivalent-circuit models are reduced, leading to a better understanding of the induction motor’s performance.

This article introduces an innovative motor testing device designed to perform various induction motor tests and demonstrates how complete electromechanical characteristics can be extracted in a short time for both industrial and research applications.

The proposed induction motor test system includes several mechanical and electrical parts. In this setup, the induction machine under test (MUT) and the driving motor (DM) are connected through a torque transducer. The shafts and couplings must withstand the mechanical stresses during the induction motor test. The measured torque signal is used both for data recording and as an input in the motor speed control of the DM. In this system, the DM is a synchronous reluctance motor rated at 2.2 kW, providing 14 N·m torque and 1500 rpm. It is supplied by a PWM inverter with a braking function and controlled through motor speed control using a dSPACE DS1104 unit.

The data acquisition system HBM GEN3i forms the core of the setup. It can simultaneously record 12 isolated channels with a sampling rate of 2 MS/s, storing torque, speed, current, and phase voltage data of the MUT without losing transient information. This precise data recording enables complete analysis of the induction motor test and evaluation of torque-speed characteristics and motor performance under different voltage and load conditions.

The data acquisition system also supports mathematical operations and filtering, allowing accurate analysis of motor startup and electromechanical characteristics during the test.

The driving motor (DM) in the induction motor test system is controlled through motor speed control. Its control scheme is implemented using vector control in the synchronous rotor reference frame (d,q). The reference speed is applied according to a predefined speed profile, and the speed feedback is measured using a 512-pulse-per-revolution encoder. The speed controller is of the proportional–integral (PI) type. Its output, combined with the measured torque, is used to generate a feedforward reference torque (Tref).

The reference torque is applied to a two-dimensional lookup table (LUT), which determines the d-axis and q-axis reference currents for internal current control. This LUT is calculated based on the magnetic model identification of the DM and the maximum torque per ampere (MTPA) operation. The DM phase currents and rotor position are measured for current control. The DC-link voltage of the inverter is considered to adjust the inverter duty cycles.

This speed control system, combined with feedforward torque, enables very high dynamic performance of the speed loop. It ensures stable speed regulation during the induction motor test without oscillations. Such precision and stability are essential for accurately determining torque-speed characteristics and evaluating the motor’s performance under various test conditions.

Schematic of the driving motor (DM) speed control in the testing system, showing vector control loop, speed feedback, and controlled current adjustment

The performance of the testing system was evaluated using a small three-phase induction motor. The motor’s nominal parameters, including power, voltage, current, number of poles, speed, and torque, are listed in Table 1. Various tests were performed on this motor to accurately evaluate electromechanical characteristics and simultaneously record electrical and mechanical data. These data allow the determination of actual torque-speed characteristics, as well as torque and current under different operating conditions.

A. Measurement of Quasi-Static Torque Characteristics

In the induction motor test, a reference speed ramp is applied through the motor speed control, and the induction machine is supplied with nominal voltage. To maintain a quasi-static state, a small acceleration is selected so that dynamic variations remain limited, although the test duration increases. The ramp time must be controlled to prevent excessive motor temperature and avoid data errors. This method enables precise torque-speed analysis and aligns perfectly with motor speed control.

To balance quasi-static conditions with thermal limitations, a two-stage speed profile is used. From standstill to near maximum torque, a faster ramp is applied to increase motor speed more quickly, and then a slower ramp is used to reach synchronous speed, ensuring more stable measurements. Preventing speed oscillations is only possible with the high dynamics of the motor speed control, which improves the quality of torque-speed curves and allows more accurate performance analysis.

At time t0, power is applied, and the driving motor holds the shaft at zero for a short interval Δt1. This brief pause allows the actual starting torque to be measured after transients subside. This method differs from the mechanical rotor test and provides clean, repeatable measurements. The nominal parameters of the induction machine are: 1500 W power, 400 V voltage, 3.8 A current, 50 Hz frequency, 4 poles, 1405 rpm speed, 10.2 N·m nominal torque, 19.8 N·m starting torque, and 26.4 N·m maximum torque.

Three startup sequences were performed at different voltages and ambient temperatures. Comparing the torque-speed curves as well as torque and current shows that the torque-voltage relationship is approximately quadratic and consistent with the equivalent circuit model, confirming the reliability of the induction motor test.

B. Locked-Rotor Test

The locked-rotor test is a standard procedure for determining the equivalent circuit parameters of an induction motor. Using the proposed testing system, this test is easily performed by setting the driving motor speed to zero. Since the motor under test is connected to a torque transducer, it is also possible to measure the starting torque at reduced voltage (locked-rotor voltage), providing engineers with precise data for equivalent circuit analysis.

C. No-Load Test at Synchronous Speed

This test enables precise determination of the magnetizing current and iron losses of the induction motor. Mechanical and windage losses are compensated by the driving motor. During this test, the mechanical speed of the motor under test is set to synchronous speed, making the motor slip nearly zero.

To achieve true zero slip, the supply frequency of the driving motor must be synchronized with the motor under test. This synchronization is achieved by connecting the drive output to the main frequency using a PLL. Any other method that does not ensure isofrequency conditions should not be used. Non-zero slip increases rotor losses and leads to inaccurate evaluation of iron losses.

D. Efficiency Test

The efficiency test is a long-duration experiment used to determine the efficiency of an induction motor. In this test, the driving motor acts as a brake, applying the rated torque to the motor under test. Using a regenerative drive, the shaft power can be fed back to the grid, and only the total system losses need to be supplied.

After completing thermal tests, the drive can be programmed to perform a variable-load test, applying a load torque profile according to international standards. The variable-load test is essential for estimating the motor’s stray load losses. At the end of the rated-load temperature test, an acceleration test can be quickly repeated to evaluate the effect of temperature on the motor’s electromechanical characteristics compared to cold conditions. For the tested three-phase induction motor, torque variations with temperature were recorded at stator winding temperatures of approximately 25°C and 105°C (measured at the end of the test).

The results show that the motor delivers a starting torque higher than the manufacturer’s rated value under both cold and hot conditions, and the designed pull-out torque at hot conditions is confirmed. Additionally, the motor’s operating point during the rated-load temperature test aligns with the measured torque-speed characteristics under hot conditions, confirming the capability of the proposed testing system to evaluate quasi-static characteristics of the motor.

Efficiency test for evaluating induction motor performance

E. Test for Rotor Time Constant Evaluation

The rotor time constant is a key parameter for estimating rotor flux in high-performance induction motor vector control. This test can be performed under the same operating conditions as the no-load test at synchronous speed. The driving motor, using speed control, applies zero slip to the motor under test. While the motor operates at synchronous speed and is supplied with rated voltage, the main switch is turned off, and the data acquisition system is used to record the voltage at the motor terminals.

When the main switch is on, the measured voltage equals the supply voltage; when it is off, the voltage corresponds to the stator electromotive force (EMF) generated by the rotor flux. The EMF amplitude decays according to a first-order system defined by the rotor time constant. Analyzing the stator EMF waveforms allows accurate evaluation of the rotor time constant, as the test is conducted under electromagnetic conditions close to real operating conditions.

Using the square root of the sum of squares of the stator components in the stationary reference frame (alpha and beta), the stator voltage decay can be calculated. The results show that the rotor time constant of the tested motor is estimated at 114 milliseconds.

Rotor time constant evaluation of an induction motor

F. Standard No-Load Test

The classic no-load test is one of the standard procedures for determining the equivalent circuit parameters of an induction motor. Performing this test does not require the proposed testing system, as the motor must rotate freely without any mechanical connection to the shaft or torque transducer.

For this test, the motor under test is mechanically disconnected from the torque transducer and driving motor shaft. The data acquisition system remains active to synchronize measurement timing with the application of supply voltage to the motor.

The testing system was used to measure the electromechanical characteristics of single-phase induction motors. The tested machines included a single-phase motor with a separable permanent capacitor, and nameplate data were recorded.

A speed ramp from 0 to 1500 rpm was applied over ten seconds to capture the motor’s dynamic behavior. The motor’s electrical and mechanical characteristics were measured during the speed ramp, and torque versus speed and current characteristics were analyzed.

During motor startup, the capacitor connected to the auxiliary winding was automatically changed from 490 µF to 30 µF. This change in capacitance caused a modification in the torque characteristics.

The torque transition due to switching from the starting capacitor to the running capacitor occurred, typically at a speed near the breakdown torque associated with the lower capacitor. The data acquisition system recorded this sudden phenomenon without issues, providing accurate results of the single-phase motor’s performance.

This article presents an induction motor testing system for determining quasi-static electromechanical characteristics under sinusoidal voltage supply. The system offers significant advantages over other solutions. Data acquisition starts from zero speed, and the motor under test is held stationary to accurately evaluate the starting torque. This is made possible by the driving motor and precise motor speed control.

The HBM GEN3i data recorder ensures complete data flow without synchronization issues and can capture transient phenomena effectively. Once recorded, the data are stored for extracting secondary parameters such as efficiency, power factor, power, and losses.

The performance of the two tested motors met expectations, and the system can record full motor characteristics in less than ten seconds. Therefore, this system provides an effective solution for the “online” validation of small- and medium-sized induction motors.